Design Two independent measuring systems, vee entry 60°
Nominal size in mm 100, 160
Accuracy class 1.6
Scale ranges 0 ... 0.6 to 0 ... 60 bar
Scale range must be selected in relation to the highest total pressure applied! In heating plants with circulating pumps, the overall pressure is usually defined as equal to the hydrostatic pressure plus the pump pressure. In order to ensure a good readability, the pressure differential to be indicated should be no less than 1/6 of the full scale range.
|
When ordering please state both pressures: a) maximum pressure applied, b) differential pressure
Pressure limitation Steady: 3/4 x full scale value Fluctuating: 2/3 x full scale value Short time: full scale value
Operating temperature Ambient: -20 ... +60 °C Medium: +60 °C maximum
Temperature effect When the temperature of the measuring system deviates from the reference temperature (+20 °C): max. ±0.4 %/10 K of full scale value
Ingress protection IP 33 per EN 60 529 / lEC 529
|