Design CE conformity: 2004/108/EG Electromagnetic compatibility (EMC) Product safety: 2001/95/EC Product safety EMC: EN 60730-1: 2002 Product safety: EN 60730-1: 2002
Adjustable range for setpoint -10 … +15 °C (Factory setting: 5 °C)
Switching difference ≤ 2 ±1 °C
Repeatability ±0.5 °C
|
Sensor active length approx. 60 cm
Switching output Changeover contact, max. 250 V AC, max. 10 A Contact material: Ag / Ni (90 % / 10 %), gold-plated (3 μm)
Permissible temperature Storage: -30 … +70 °C Ambient: -30 … +70 °C, max. 85 % rH, non-condensing Medium: w + minimum 2 K … 70 °C (w = selected setpoint)
Ingress protection IP 65 per EN 60529 / lEC 529
|